When the equipment in the workshop suddenly stops and "safety light curtain failure" pops up on the operation screen, panic is the biggest enemy. A standardized disposal process can not only resume production as quickly as possible, but also avoid secondary accidents caused by misoperation.
Phase One: Emergency Response and Safety Isolation (Stop & Notify)
Goal: Prevent secondary accidents and protect personnel safety.
1. Stop the machine immediately and do not force reset. Once any abnormality in the light curtain is found (such as abnormal flashing of the indicator light and failure to start the equipment), stop the operation of the equipment immediately . Operators are strictly prohibited from short-circuiting lines, blocking signals, or forcibly blocking the light curtain with objects in order to rush work. This is the red line!
2. When the notification is in place , notify the shift leader and equipment maintenance personnel, and inform nearby colleagues that the work station is in a 'fault pending repair' status, and a 'no operation' warning sign is hung.
3. Initial judgment record observation and record the fault symptoms:
Is the power light not on? Or is the sync light flashing?
Is there an error code on the screen?
Is the failure sporadic or persistent?
(Suggestion: Take photos and save them for later analysis)
The second stage: on-site investigation and cause location (Check & Locate)
Goal: Quickly locate whether it is a "flaw" or a "soft disease".
1. Check the power supply (Power)
lLook at the indicator light : Check whether the power indicator light (usually green light) of the transmitter and receiver is on.
l Measure voltage : If it does not light up, use a multimeter to measure whether the input voltage is within the rated range (such as DC 24V±10%). Rule out external circuit breaker tripping or virtual connection.
2. Optical Path
lClean the lenses : Use a dust-free cloth to gently wipe the lenses at the transmitter and receiver. Oil, dust, and iron filings are the number one killers of light curtains.
lLight calibration : Observe the alignment indicator light (Alignment LED). If the indicator light is red or flashing, the optical axis is misaligned. Loosen the bracket and fine-tune the angle until the indicator light turns solid green.
l Measuring distance : Confirm whether the installation distance is within the nominal protection distance range of the light curtain. Too far will cause signal attenuation.
3. Check Connection
l Check the cables : Check whether the signal cables and power cable connectors are loose, detached, or pulled.
lCheck shielding : Check whether the shielding layer is well grounded. Poor grounding or damaged shielding will cause electromagnetic interference (EMI) to the inverter and servo motor, causing the light curtain to malfunction.
4. Check the environment (Environment)
lAvoid strong light : Check whether there is interference from direct sunlight or strong strobe light (such as welding arc light).
lReflective removal : Check whether there are highly reflective objects (such as stainless steel plates, mirrors) behind the light curtain. If necessary, paste a frosted film or adjust the installation angle.
The third stage: functional testing and repair verification (Test & Verify)
Goal: Confirm that the repair is effective and functionality returns to normal.
1. Refer to the manual for sensitivity adjustment and fine-tune the sensitivity according to actual working conditions (note: non-professionals should not do this). Usually it is to eliminate the interference of tiny dust, or to adapt to the detection of transparent objects.
2. Blackout test (required) After repair, a full coverage test must be performed:
lUse a test stick (or finger) to block each beam in turn.
l Confirm that every blockage can immediately trigger an emergency stop or alarm for the equipment.
lAfter confirming that the occlusion is lifted, the device needs to be manually reset before it can be restarted (this is the key to safety logic).
3. Under the premise of ensuring safety, the linkage test is performed without load, and a complete cycle is observed to confirm that the light curtain is in a stable state.
The fourth stage: Upgrade maintenance and long-term prevention (Maintain & Prevent)
Goal: If you are unable to self-study, seek professional support; establish a long-term mechanism.
1. Contact the manufacturer/repair If the above steps are ineffective, sort out the fault phenomenon, troubleshooting records (preferably with photos/videos), and contact the manufacturer's technical support. If it needs to be returned to the factory, mark the disconnection to prevent wiring errors during reassembly.
2. To evaluate the life , ask the manufacturer about the theoretical life of the light curtain (usually 5-10 years or tens of millions of on-off times). If the equipment is old and malfunctions frequently, it is recommended to replace it with new ones directly to avoid working while sick.
3. Establish an inspection system
lDaily inspection : Clean the lenses before work and perform a shading test.
l Weekly inspection : Check the cable tightening and check whether the bracket is loose.
l Quarterly inspection : Check the grounding resistance and verify whether the safety distance has changed.
Maintenance tips (recommended to print and post)
Stop once, report twice, and check three times. Look at the light path first and then check the line. The lenses should be kept clean and free from dust, and the shading test should be done every day. It is strictly forbidden to short-circuit to ensure safety, and please follow the instructions during operation.
Common faults quick reference (Quick Reference)
Fault phenomenon | Possible reasons | solution |
The power light does not light up | Power outage, blown fuse, virtual connection | Check the supply voltage, replace the fuse, and tighten the terminals |
Sync light flashes/red | The optical axis is not aligned, the distance is too far, the lens is dirty | Clean the lens, fine-tune the light, and shorten the installation distance |
Output exception/no action | Load short circuit, internal circuit damage, sensitivity too low | Check the load, adjust the sensitivity, and return to the factory for repair |
Frequent false alarms | Electromagnetic interference, ambient light interference, excessive vibration | Check shielding grounding, block external light sources, and reinforce brackets |